Yaskawa A1000 VFD repair and fault codes

Yaskawa A1000 repair, common fault-code families, and first checks. Send a nameplate photo and the alarm text. Replacement units quoted on request.

The Yaskawa A1000 is a general-purpose AC drive used on fans, pumps, conveyors and many process lines. When it trips, the digital operator shows a short code such as oC, ov or GF. That code is the drive’s record of why it stopped. It is not a complete diagnosis on its own.

Star Automations repairs A1000 units at component level and tests them before dispatch. Multi-brand servo motor and drive repair is our lead work, including Yaskawa servo motors and SERVOPACKs, so a matched motor and drive can be looked at together when the alarm is not only in the VFD. Work is done under ISO 9001:2015. Every repair carries a warranty; terms are on the quote.

This page is not a copy of the technical manual, and it is not a stock list. Repair and fault-code reading come first. If a replacement is the better path, it is quoted on request.

Safe first checks

Have this work done by a qualified person.

  1. Isolate the supply and wait the discharge time on the drive warning label and in the A1000 manual before covers come off.
  2. Read the code from the digital operator and write it down before you reset it. Photograph the nameplate and the display.
  3. Check incoming supply, fuses, and the tightness of the input and motor connections.
  4. Check cabinet airflow and the cooling fan if the code points to heat.
  5. Do not keep resetting an overcurrent, ground-fault or short-circuit code if it returns. Repeated resets can add damage.

Common A1000 fault codes

Names in the table are taken from Table 5.2, Fault Detection, in the Yaskawa A1000 Quick Start Guide, TOEP C710616 41G (August 2019). First-check wording is ours. The Technical Manual, SIEP C710616 41H (March 2022), is the fuller reference for causes, parameter numbers and model-specific notes. Codes we did not confirm in that QSG table are left out.

Operator code Name What to check first
oC Overcurrent The drive has seen output current above its overcurrent level. Check the motor load, acceleration, and the motor cable and connections. If the code returns, the power section may need bench work.
ov Overvoltage The DC bus has gone above the overvoltage level. Check deceleration, the braking resistor or transistor if fitted, and whether the supply is high.
Uv1 DC Bus Undervoltage The DC bus fell too low while the drive was running. Check incoming supply, fuses and input wiring.
Uv2 Control Power Supply Voltage Fault The control-circuit supply is too low. Check the control power input; if the supply is healthy, the drive should come off for bench work.
Uv3 Undervoltage 3 (Soft-Charge Bypass Relay Fault) The soft-charge bypass path has failed. This is an internal fault; send the drive for inspection.
GF Ground Fault Output current to earth has exceeded the detection level (detection depends on the ground-fault setting). Check motor and cable insulation before resetting again.
PF Input Phase Loss An input phase is open or the supply is badly unbalanced. Check incoming power and fuses.
LF Output Phase Loss A phase is missing on the output side. Check the motor cable and motor connections.
LF2 Output Current Imbalance One or more output phases are lost or badly unbalanced. Check output wiring and motor windings.
SC Output Short Circuit or IGBT Fault A short circuit or ground fault has been detected in the output stage. Do not keep resetting. This detection is listed for later A1000 software (PRG: 1015 and after) in the QSG.
oH Heatsink Overheat The heatsink has gone past the overheat pre-alarm level. Check ambient temperature, cabinet airflow and the load.
oH1 Overheat 1 (Heatsink Overheat) The heatsink has reached the drive overheat level. Check cooling and load; a failed fan is a common cause.
FAn Internal Fan Fault The internal fan or a related contactor path has failed. Replace the fan path; do not keep running the drive without cooling.
oL1 Motor Overload The electronic motor-overload function has tripped. Check the load, the motor data and whether the motor can turn freely.
oL2 Drive Overload The drive’s own thermal protection has tripped. Check load, carrier-frequency settings only if you already work with them, and cooling.
oL3 Overtorque Detection 1 Output has stayed above the torque-detection level for longer than allowed. Check the machine for a jam and the detection settings.
rr Dynamic Braking Transistor The built-in braking transistor has failed. The drive should be inspected on the bench.
rH Braking Resistor Overheat Braking-resistor protection has tripped (when that function is enabled). Check the resistor, duty and deceleration.
CE MEMOBUS/Modbus Communication Error Control data was not received in time. Check the serial wiring, shielding and the controller.
bUS Option Communication Error Communication with an option card or the assigned controller was lost. Check the option card seating and the fieldbus cable.
EF0 Option Card External Fault An external fault was reported through an option card. Check the upstream device first.
EF1 to EF8 External Fault (input terminals S1 to S8) An external-fault input is active on that terminal. Check the wired device and the input assignment.
CPF02 to CPF25 Control circuit and board faults These codes point to an internal control, memory, clock or connection problem. Cycle power only as a first observation; if the code remains, the drive should come off for bench work.
STo Pull-Out Detection The motor has pulled out or exceeded its pull-out torque. Check the load, the motor data and whether the application is asking more than the motor can hold.

Yaskawa servo A.xxx alarms are a different family. Those belong to SERVOPACKs, not to the A1000 keypad. See the Yaskawa servo pages linked below.

Repair, test and supply

A1000 repairs typically involve the power section, cooling fan, control board, current detection or the braking transistor, after the supply and motor have already been checked. Units are tested before dispatch.

Email star@starautomations.com or WhatsApp +91 97866 22233 with the nameplate photo and the alarm text. Collection and the receiving location are stated on the quote. Locations: Puducherry, Chennai, Bengaluru, Hyderabad and Delhi.

If a replacement A1000 is required, write to sales@starautomations.com. Supplied new, surplus or refurbished on request, subject to availability.

Related pages: VFD repair in India, Yaskawa VFD repair in Bengaluru, Yaskawa servo motor repair, Yaskawa servo drive repair, Yaskawa Sigma-7, Yaskawa Sigma-III and Sigma-5, the industrial fault-code hub, and contact.

Sources

Operator codes and names were checked against the Yaskawa A1000 Quick Start Guide, TOEP C710616 41G, Table 5.2 Fault Detection. The Yaskawa A1000 Technical Manual, SIEP C710616 41H, is the fuller series reference. First-check wording is Star’s. This page is not a substitute for the manual of the firmware you have.

Frequently asked questions

What does an A1000 fault code mean? It is the drive’s record of why it stopped. Read the exact operator code (for example oC or Uv1) and write it down before you reset.

Is oC the same as an ABB F0001 or 2310? They are both overcurrent trips, but they belong to different makers and manuals. Use this page for A1000, and the ABB drive fault-code guide for ACS550 and ACS580.

Can I reset GF or SC and run again? Only after the motor, cable and earth path have been checked. If the same code returns, the drive or the motor circuit still has a fault. Do not keep resetting a short-circuit or IGBT code.

Do you repair A1000 units in India? Yes. Send the nameplate and alarm photos to star@starautomations.com or WhatsApp +91 97866 22233.

Can you supply an A1000 if ours is not repairable? Supplied new, surplus or refurbished on request, subject to availability. Use sales@starautomations.com.

Do you also repair Yaskawa servo motors and SERVOPACKs? Yes. Multi-brand servo motor and drive repair is core work, including the Yaskawa servo series on their own pages linked above. Motors can be tested on a universal servo test system covering 180+ motor models.

Are A.400 and A.410 A1000 codes? No. Those A.xxx codes are Yaskawa servo / SERVOPACK alarms. See the Yaskawa A.400 and A.410 guides, or the guides library.

Do you repair A1000 units used in Bengaluru? Yes. There is also a Yaskawa VFD repair page for Bengaluru. Work can be sent or handed over at Puducherry, Chennai, Bengaluru, Hyderabad or Delhi, as advised on the quote.

Is this a complete list of A1000 codes? No. It is a verified subset of commonly seen faults from the QSG fault table. Model-specific notes, auto-tuning codes and option-card codes are in the technical manual.

What should I send with the enquiry? A nameplate photo, the operator code as shown, and a short note on whether the drive tripped at start, while running, or while stopping.

Where are your locations? Puducherry, Chennai, Bengaluru, Hyderabad and Delhi.