Star Automations repairs Danfoss drives, including VLT FC 302, FC 102, FC 202, in India. We read the fault code, repair the drive, check motor feedback on Mitchell test systems, and arrange a retrofit, exchange or alternative when the drive is obsolete. Send the nameplate and the code.

  • 26years of servo repair, since 2000
  • 3,000+customers across India
  • 100+servo brands covered by our universal servo motor test equipment
  • 5sites: Puducherry, Chennai, Bengaluru, Hyderabad, Delhi

Every repaired unit returns with a printed test report.

How a repair starts

Send the nameplate photo on WhatsApp +91 97866 22233 for a repair assessment.

Every repaired unit is tested on our bench and returns with a printed test report. Timing depends on the fault and the parts, and is stated on the quote.

  • Send the nameplate photo on WhatsApp +91 97866 22233 for a repair assessment
  • Printed test report with every motor
  • Every repair carries a warranty; terms are on the quote.
  • Pickup can be arranged; parts that must be imported are quoted with their own timeline
01At a glance

How a Danfoss drive works and where it fails

Every servo drive and inverter, including Danfoss, turns mains AC into DC, stores it in the DC bus, and chops it with IGBTs to drive the motor, while the control board reads the feedback device. Faults show up at seven points. Match the numbered point in the picture to the sections below.

Servo drive anatomy and common failure pointsMains supply, rectifier, DC bus capacitors, IGBT inverter and motor, with the control board, feedback loop and braking resistor. Numbers mark the common failure points.AC mainsRectifierAC to DCDC buscapacitorsIGBT inverterpower stageMotorwinding, cableBraking resistorControl board and gate driveCPU, parameters, fieldbusEncoder / resolver1234567
  • 1 Input rectifier and fuses: phase loss, shorted diodes
  • 2 DC-bus capacitors: ageing, under-voltage, ripple
  • 3 IGBT power stage: over-current, short circuit, gate-drive faults
  • 4 Motor and cable: winding or insulation failure, earth fault
  • 5 Encoder or resolver: feedback, mismatch and noise faults
  • 6 Control board: memory, parameter and communication faults
  • 7 Braking chopper and resistor: over-voltage on stopping
02Models

Models and series we repair

Series or modelWhat it isNotes
VLT AutomationDrive FC 301 and FC 302Motion and industrial driveAlarms are numbered
VLT HVAC Drive FC 102HVAC driveFans and pumps in buildings
VLT AQUA Drive FC 202Water and wastewater drivePumps
VLT Micro Drive FC 51Compact driveSmall machines
VLT 5000Earlier VLT rangeOlder installations
VaconDrive range now part of DanfossIndustrial and marine
03Error codes

Danfoss error codes and what to do

Danfoss VLT drives show an alarm number. Other VLT ranges use different numbering, so check your manual. Tap an alarm for the causes and safe checks.

Communication and fieldbus

Alarm 2Signal fault (live zero)

Likely causes: An analog input fell below half of its programmed minimum, usually a wire break or a failed transmitter. Measure the signal at the terminal first.

Safe checks you can do:

  • Confirm the PLC or controller is running
  • Check the cable, connectors and termination
  • Check addresses for duplicates
  • Check the option module is seated and read its LEDs

Send it to us when: the option card or the drive communication circuit is suspected.

Alarm 17Control word timeout

Likely causes: The fieldbus control word is no longer updating.

Safe checks you can do:

  • Confirm the PLC or controller is running
  • Check the cable, connectors and termination
  • Check addresses for duplicates
  • Check the option module is seated and read its LEDs

Send it to us when: the option card or the drive communication circuit is suspected.

Under-voltage and phase loss

Alarm 4Mains phase fault

Likely causes: The incoming supply has a missing or badly unbalanced phase.

Safe checks you can do:

  • Measure all three supply phases under load
  • With the supply off and locked out, check input fuses and terminal tightness
  • Check the input contactor and any upstream breaker
  • Note whether the trip happens at power-up, on enable or during acceleration

Send it to us when: the supply is healthy but the trip persists.

Alarm 8DC under-voltage

Likely causes: The DC link is too low from a supply sag or interruption. Check the upstream supply and loose input terminals.

Safe checks you can do:

  • Measure all three supply phases under load
  • With the supply off and locked out, check input fuses and terminal tightness
  • Check the input contactor and any upstream breaker
  • Note whether the trip happens at power-up, on enable or during acceleration

Send it to us when: the supply is healthy but the trip persists.

DC bus over-voltage

Alarm 7DC over-voltage

Likely causes: The DC link is too high from a rapid stop of a high-inertia load or a mains spike. Lengthen the ramp, enable over-voltage control, or add a braking resistor.

Safe checks you can do:

  • Lengthen the deceleration ramp
  • Confirm a braking resistor is fitted, wired and of the value the manual requires
  • Measure the supply voltage and look for surges when large loads switch
  • Note whether the trip happens only during stopping

Send it to us when: the trip continues with a good resistor and a long ramp.

Overload, stall and I2t

Alarm 9Inverter overloaded

Likely causes: The drive ran too long above its rated current. Check the load, then confirm the motor data matches the nameplate.

Safe checks you can do:

  • With the supply off, turn the motor shaft by hand and check the machine moves freely
  • Check the motor brake releases when enabled
  • Compare the motor current and rating parameters with the nameplate
  • Look for jams or coupling damage

Send it to us when: the mechanics are free and the settings match the nameplate.

Alarm 12Torque limit

Likely causes: Output torque reached the set limit.

Safe checks you can do:

  • With the supply off, turn the motor shaft by hand and check the machine moves freely
  • Check the motor brake releases when enabled
  • Compare the motor current and rating parameters with the nameplate
  • Look for jams or coupling damage

Send it to us when: the mechanics are free and the settings match the nameplate.

Motor thermistor and temperature sensor

Alarm 10Motor ETR over-temperature

Likely causes: The electronic thermal model reached its limit. Check for overload, and that the motor parameters match the nameplate. Run the automatic motor adaptation.

Safe checks you can do:

  • Confirm the motor is really hot
  • Check the motor cooling fan
  • With the supply off, check thermistor continuity against the manual
  • Check the thermistor type parameter

Send it to us when: the motor is cool and the wiring is good.

Alarm 11Motor thermistor over-temperature

Likely causes: A connected motor thermistor has tripped.

Safe checks you can do:

  • Confirm the motor is really hot
  • Check the motor cooling fan
  • With the supply off, check thermistor continuity against the manual
  • Check the thermistor type parameter

Send it to us when: the motor is cool and the wiring is good.

Over-current, short circuit, earth fault

Alarm 13Over-current

Likely causes: The peak current limit was exceeded by a blockage, a short ramp or a fault. Check the mechanics first, then the ramp, then the motor cable.

Safe checks you can do:

  • With the supply off, locked out and the DC bus discharged as the manual states, disconnect the motor cable from the drive
  • Measure motor and cable insulation to earth with a megger; very low readings (around or below 1 MOhm) point to damaged insulation
  • Inspect the motor terminal box, glands and connectors for water, oil or burn marks
  • Check the load turns freely and lengthen the acceleration ramp if it is too short

Send it to us when: the trip returns with the motor cable disconnected, or the drive trips on power-up or enable.

Alarm 14Earth fault

Likely causes: Leakage current from an output phase to earth. With the drive isolated and discharged, disconnect the motor cable and measure the insulation resistance of the motor and the cable. Repair damage or moisture before restarting.

Safe checks you can do:

  • With the supply off, locked out and the DC bus discharged as the manual states, disconnect the motor cable from the drive
  • Measure motor and cable insulation to earth with a megger; very low readings (around or below 1 MOhm) point to damaged insulation
  • Inspect the motor terminal box, glands and connectors for water, oil or burn marks
  • Check the load turns freely and lengthen the acceleration ramp if it is too short

Send it to us when: the trip returns with the motor cable disconnected, or the drive trips on power-up or enable.

Alarm 16Short circuit

Likely causes: A short at the motor output or inside the drive. It needs a full power cycle with the DC link fully discharged before reset.

Safe checks you can do:

  • With the supply off, locked out and the DC bus discharged as the manual states, disconnect the motor cable from the drive
  • Measure motor and cable insulation to earth with a megger; very low readings (around or below 1 MOhm) point to damaged insulation
  • Inspect the motor terminal box, glands and connectors for water, oil or burn marks
  • Check the load turns freely and lengthen the acceleration ramp if it is too short

Send it to us when: the trip returns with the motor cable disconnected, or the drive trips on power-up or enable.

Alarm 30, 31, 32Motor phase U, V or W missing

Likely causes: An open output phase between the drive and the motor. Check the motor cable and terminals with the supply locked out.

Safe checks you can do:

  • With the supply off, locked out and the DC bus discharged as the manual states, disconnect the motor cable from the drive
  • Measure motor and cable insulation to earth with a megger; very low readings (around or below 1 MOhm) point to damaged insulation
  • Inspect the motor terminal box, glands and connectors for water, oil or burn marks
  • Check the load turns freely and lengthen the acceleration ramp if it is too short

Send it to us when: the trip returns with the motor cable disconnected, or the drive trips on power-up or enable.

Over-temperature

Alarm 29Heatsink over-temperature

Likely causes: The power module is too hot from cooling or ambient. With the drive isolated and discharged, clean the heatsink and check the fan and ventilation.

Safe checks you can do:

  • Confirm the cooling fan runs and spins freely
  • With the supply off, clean the heatsink and cabinet filters
  • Check clearance around the drive and the ambient temperature
  • Reduce the load or the switching frequency if the manual allows it

Send it to us when: the fan and airflow are good but the drive still overheats.

Memory, parameter and internal faults

Alarm 38Internal fault

Likely causes: An internal drive fault with a subcode that identifies the subsystem. It needs a power cycle with the bus discharged.

Safe checks you can do:

  • Power cycle the drive after discharge time
  • Restore defaults and reload your backed-up parameters
  • Improve shielding and earthing of control wiring
  • Record the full fault history before resetting

Send it to us when: the fault returns after a reset, which points to hardware.

Safety first. Only a qualified person should open or measure a drive. Dangerous voltage stays on the DC bus after the supply is switched off. Lock out the supply, wait for the discharge time stated in the manual and confirm the bus is discharged before touching anything.

04Diagnosis

Fault diagnosis in four steps

  1. Read and recordNote the code, the last faults in the history, what the machine was doing and any LEDs or sounds. Take photos of the display and nameplates.
  2. Safe visual checksSupply off, locked out, bus discharged. Look for burn marks, swollen capacitors, dirt, loose terminals, damaged cables and wet connectors.
  3. Isolate the partMotor and cable, feedback, supply or drive? Disconnecting the motor cable and re-testing separates a drive fault from a motor or cable fault.
  4. DecideFixed by a safe check? Back to work. Not fixed? Send the nameplate and code. We repair it or arrange the alternative.
05Self-help

Check these yourself before you send it

  • Power: measure all three phases, check fuses and terminals with the supply locked out
  • Cooling: clean the heatsink and filters, confirm the fan runs
  • Cables: inspect motor power and feedback cables and connectors for damage
  • Settings: compare motor and feedback parameters with the motor nameplate
  • Load: turn the shaft by hand with power off and check the brake releases
  • Backups: save the parameter file and fault history before any reset
  • Prevent repeats: keep the cabinet clean and cool, replace fans on schedule, and keep spare parameters backed up
06Alternatives

Repair or alternative? What to do when the drive is not available

Fault code and nameplate
Safe checks
Send to Star
Inspect and quote
Repair and test
Or: retrofit, exchange, source, remanufacture
OptionWhen it fitsWhat we do
RepairThe drive is repairableWe inspect, repair and check it, then return it. Every repair carries a warranty; terms are on the quote.
ExchangeThe machine cannot waitAsk us about an exchange unit. See the advance exchange page.
Retrofit with an equivalent driveThe model is obsolete or not availableWe match power, feedback type, command interface and fieldbus, then fit a different drive to the same motor.
Motor and drive upgradeBoth parts are old or mismatchedWe propose a matched motor and drive pair and help with parameters.
Source surplus or refurbishedYou want the same modelWe search for the exact part through our sourcing network and partners abroad.
Remanufacture the boardsNo replacement exists in the marketWe rebuild the power or control board. We have reverse engineered and rebuilt obsolete boards.
Parameter recoverySettings are lost or the memory is corruptWe help to rebuild the parameter set from the nameplate and the machine data.

If the drive is no longer sold, match these five things

  • Power and voltage: rated current, supply voltage and overload need
  • Feedback type: encoder, resolver, Hiperface, EnDat, BiSS, absolute or incremental
  • Command interface: analog, pulse and direction, CANopen, EtherCAT, Profibus, Profinet, Modbus
  • Mechanical fit: size, mounting, connectors and cable lengths
  • Safety and braking: safe torque off, brake output and braking resistor

Send these details with the nameplate and we propose a route. A cross-reference is given where one exists. See also advance exchange.

07Testing

How the drive and motor feedback are checked

  • Feedback test: Mitchell Electronics TI-5000JX and TI-3000JX universal servo test systems read the encoder, resolver or sensor signals
  • Waveform check: special encoder test oscilloscope to inspect the feedback signal
  • Fault finding: diagnosis tool, special diagnosis tool and feedback diagnosis tool
  • Inspection and functional check: the unit is checked before it is returned
  • Warranty: every repair carries a warranty; terms are on the quote
→How it works

From nameplate photo to a tested motor in 7 steps

One route for servo motors, encoders and drives. You see the price before any work starts, and the report before the unit leaves our bench.

  1. 1 · Nameplate photoSend it on WhatsApp or the form
  2. 2 · Repairable? QuoteWe assess the nameplate photo and confirm whether the unit is repairable.
  3. 3 · Courier or pickupThe unit reaches our bench
  4. 4 · Bench diagnosisInsulation, windings, brake, encoder
  5. 5 · RepairFailed parts, bearings, seals, brake
  6. 6 · Align and run-testEncoder aligned; no-load and load run
  7. 7 · Report and dispatchPrinted test report with the unit
  8. Line down?Servo Swap ships a tested unit first. How Servo Swap works

Timing depends on the fault and the parts, and is stated on the quote.

09FAQ

Danfoss drive repair FAQ

Do you repair Danfoss drives?

Yes. We repair Danfoss drives and inverters. Send the nameplate, the fault code and a photo of the display, and we confirm the route before you courier anything.

Which Danfoss models and series do you repair?

VLT AutomationDrive FC 301 and FC 302, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT Micro Drive FC 51, VLT 5000, Vacon. If your model is not listed, send the nameplate.

My Danfoss drive shows Alarm 2. What does it mean?

Signal fault (live zero). Check the safe steps above first. If the fault returns, send the drive to us.

Can I fix a Danfoss drive fault myself?

You can do the safe checks: supply, fuses, cooling, cables, settings and the load. Do not open the drive or measure inside it unless you are qualified, because the DC bus stays live after switch-off.

What if my Danfoss drive is obsolete or not available?

We repair it, arrange an exchange, retrofit a different drive that matches the power, feedback and command interface, source the same model, or remanufacture the board.

Can you retrofit a different drive to my motor?

Yes, when the power, feedback type, command interface and mounting match. Send the nameplates of the drive and the motor.

Is there a warranty?

Every repair carries a warranty; terms are on the quote.

Are you an OEM service centre?

No. Star Automations is an independent multi-brand repair company and is not an OEM service centre.

Brand names are trademarks of their owners. Star Automations is an independent multi-brand company and is not an OEM service centre. Code lists are general guides; the manual for your exact unit is the authority.

Send the nameplate and the code. We confirm the route first.

WhatsApp a photo of the drive nameplate and display to +91 97866 22233, or email admin@starautomations.com.