WEG CFW Drive Fault Codes: Meaning, Causes and When to Send for Repair

Common WEG CFW fault codes and what to do about themA WEG CFW drive fault code tells you which protection tripped, not which part failed. This guide lists the common codes, what usually causes them, what to check first, and the point at which the drive needs bench repair.

Fault codeFirst checksBench repair
Schematic only.

Important: Star Automations is a WEG service partner. It is also an independent multi-brand repair company and is not an OEM service centre. Work described on this page is carried out by Star Automations. WEG is a trademark of its owner. Star Automations does not give warranty terms on this page; scope and conditions are confirmed for each job.

01Codes

Common fault codes

Common WEG CFW fault codes
CodeNameUsual causesFirst safe checks
F021DC link undervoltageLow or unstable input supply, failed pre-charge circuit, undervoltage setting above supplyCheck supply voltage and phases; repeated trips with good supply point to the pre-charge or DC bus
F022DC link overvoltageRegeneration from the load, deceleration ramp too short, supply too highLengthen the deceleration ramp; check braking resistor and supply
F071Output overcurrentExcessive load, acceleration ramp too short, current limit set too highCheck mechanical load and ramps; disconnect the motor and see if the trip remains
F072Motor overloadExcessive shaft load, motor overload parameters set too low for the motorCheck load, motor current and the overload parameters
F074Ground faultShort to earth on an output phase, motor cable capacitance on long cablesCheck motor and cable insulation before any restart
F051IGBT overtemperatureBlocked heat sink, failed fan, high ambient, overloadClean the heat sink, check the fan and ventilation
F078Motor overtemperatureMotor temperature sensor (PTC) trip from overload or poor coolingCheck motor cooling and the sensor wiring
F006Input voltage imbalance or phase lossMissing phase, loose input connection, unbalanced supplyCheck the input fuses, contactors and supply phases

Fault numbering and wording can differ by drive series and firmware version. Always check the manual for your exact drive. WEG is a trademark of its owner.

02Repeated

When a fault keeps coming back

A fault that clears after a fix is a settings or load problem. A fault that returns with the motor disconnected, or at power-up, usually points to the drive itself: output switching devices, gate-drive circuits, pre-charge, DC bus capacitors or the control board. Repeated resets on a drive with a failing power stage can damage more parts, so stop and arrange an assessment.

  • Overcurrent or ground fault with the motor disconnected
  • Undervoltage or overvoltage trips with a healthy supply
  • Blank display or no response at power-up
  • Burnt smell, swollen capacitors or visible damage
03Send

What to send for an assessment

What to send: photo of the nameplate or rating label, full model code and serial number, the fault or alarm code on the display, what happened before the failure, your location and how urgent it is.

See our WEG CFW drive repair page.

90Questions

Frequently asked questions

What does fault F021 mean on a WEG CFW drive?

F021 is DC link undervoltage: the DC bus fell below its minimum. Common causes are low or unstable supply voltage, a failed pre-charge circuit or an undervoltage parameter set above the supply. Check the supply first. If it repeats with a healthy supply, the drive needs assessment.

What does fault F071 mean on a WEG CFW drive?

F071 is output overcurrent. It is commonly caused by excessive load, an acceleration ramp that is too short or a current limit set too high. Disconnect the motor and see if the trip remains; if it does, the drive output stage may be at fault.

What does fault F074 ground fault mean?

F074 indicates a short to earth on one or more output phases, or high motor cable capacitance causing current peaks. Check motor and cable insulation before restarting. Restarting repeatedly into a ground fault can damage the output stage.

Should I keep resetting a drive that trips?

No. If a trip clears once after you fix the cause, that is normal. If it repeats with the motor disconnected or at power-up, stop resetting and arrange an assessment, because repeated resets can damage the power stage further.