Short answer:** A single-phase VFD takes a 230 V single-phase supply and gives a variable-frequency three-phase output, so a small three-phase motor can run where only single-phase power is available. Star Automations supplies VFDs by model and motor size, and repairs them. Supplied new, surplus or refurbished on request, subject to availability.
01 HP to kW sizes
| Motor HP | Motor kW (nominal) | Usual drive input |
|---|---|---|
| 0.5 HP | 0.37 kW | Single-phase 230 V available |
| 1 HP | 0.75 kW | Single-phase 230 V available |
| 1.5 HP | 1.1 kW | Single-phase 230 V available |
| 2 HP | 1.5 kW | Single-phase 230 V available |
| 3 HP | 2.2 kW | Single-phase 230 V available in many ranges |
| 5 HP | 3.7 kW | Mostly three-phase 400 V |
| 7.5 HP | 5.5 kW | Three-phase 400 V |
| 10 HP | 7.5 kW | Three-phase 400 V |
1 HP is about 0.746 kW. Size the drive by the motor full-load current on the nameplate, not by HP alone, and allow a larger drive for heavy starting loads. Single-phase input ranges stop at a size set by each maker; check the catalogue for the exact limit.
02 How to wire the motor
- The output of a single-phase-input VFD is three-phase at about 230 V.
- A three-phase motor marked 230/400 V must be connected in delta (230 V) for this drive.
- A motor marked 400/690 V cannot be run at full power from a 230 V output.
- Standard VFDs are made for three-phase motors. Do not connect a single-phase capacitor-start motor unless the drive maker says it is suitable.
03 Single-phase supply, three-phase drive?
Some three-phase input drives can run from a single-phase supply only if the maker's manual allows it, and then usually at a reduced rating. Send the model and we check the manual.
04 What to send for a quote
Motor kW or HP, motor full-load current and voltage, supply (single or three-phase), the application (fan, pump, conveyor, machine) and the quantity. To replace an existing drive, send its full model number.
Browse listed VFDs in the online shop.
06 Frequently asked questions
What is a single-phase VFD?
A variable frequency drive that runs from a single-phase 230 V supply and gives a three-phase output to control the speed of a three-phase motor.
Can a single-phase VFD run a three-phase motor?
Yes. Connect a 230/400 V motor in delta for the 230 V three-phase output, and size the drive by the motor full-load current.
Which VFD do I need for a 1 HP motor?
A 0.75 kW drive is the usual size for a 1 HP motor, chosen by the motor full-load current and the starting load. Single-phase input models are common at this size.
Are 5 HP and 10 HP VFDs available with single-phase input?
Mostly not. At 3.7 kW and above most drives use a three-phase 400 V supply. Some makers allow a three-phase drive on single phase with derating; check the manual.
Do you repair single-phase VFDs?
Yes, power stage, control board and supply faults. Every repair carries a warranty; terms are on the quote.
07 Send the part number for a quote
Share the part number, a clear photo of the label and the quantity. We reply with what we can supply.
Supplied new, surplus or refurbished on request, subject to availability.
- WhatsApp: +91 97866 22233
- Supply: sales@starautomations.com
- Repair: star@starautomations.com
- Form (part number, photo, quantity or BOM): /parts-request/
Every repair carries a warranty; terms are on the quote. Service locations: Puducherry, Chennai, Bengaluru, Hyderabad and Delhi.
ISO 9001:2015 · 3,000+ customers · 100+ brands · 100+ engineers · GeM vendor · universal servo test system for 180+ motor models.
*Brand names and part numbers are trademarks of their owners and are used only to identify compatible products; Star Automations is an independent supplier and repair provider.*